Minggu, 02 November 2008

Control Respon (2)

Proportional Control
A proportional control response produces an analog or variable output change in proportion to a varying input. In this control response, there is a linear relationship between the input and the output. A setpoint, throttling range and action typically define this relationship. In a proportional control response, there is a unique value of the measured variable that corresponds to full travel of the controlled device and a unique value that corresponds to zero travel on the controlled device. The change in the measured variable that causes the controlled device to move from fully closed to fully open is called the throttling range. It is within this range that the control loop will control, assuming that the system has the capacity to meet the requirements.

The action dictates the slope of the control response. In a direct acting proportional control response, the output will rise with an increase in the measured variable. In a reverse acting response, the output will decrease as the measured variable increases. The setpoint is an instruction to the control loop and corresponds to a specified value of the controlled device, usually half-travel. An example is shown in Figure 5.
In a proportional control system, the value of the measured variable at any given moment is called the control point. Offset is defined as the difference between the control point and the desired condition. One way to reduce offset is to reduce throttling range. Reducing the throttling range too far will lead to instability. The more quickly the sensor “feels” the effect of the control response, the larger the throttling range has to be to produce stable control.

Proportional plus Integral (PI) Control
PI control involves the measurement of the offset or “error” over time. This error is integrated and a final adjustment is made to the output signal from the proportional part of this model. This type of control response will use the control loop to reduce the offset to zero. A well set-up PI control loop will operate in a narrow band close to the setpoint. It will not operate over the entire throttling range (Figure 6).
PI control loops do not perform well when setpoints are dynamic, where sudden load changes occur or if the throttling range is small.

Proportional plus Integral plus Derivative (PID) Control
PID control adds a predictive element to the control response. In addition to the proportional and integral calculation, the derivative or slope of the control response will be computed. This calculation will have the effect of dampening a control response that is returning to setpoint so quickly that it will “overshoot” the setpoint.

PID is a precision process control response and is not always required for HVAC applications. The routine application of PID control to every control loop is labor intensive and its application should be selective.

Definition of Direct Digital Control (DDC)


DDC control consists of microprocessor-based controllers with the control logic performed by software. Analog-to-Digital (A/D) converters transform analog values into digital signals that a microprocessor can use. Analog sensors can be resistance, voltage or current generators. Most systems distribute the software to remote controllers to eliminate the need for continuous communication capability (stand-alone). The computer is primarily used to monitor the status of the energy management system, store back-up copies of the programs and record alarming and trending functions. Complex strategies and energy management functions are readily available at the lowest level in the system architecture. If pneumatic actuation is required, it is accomplished with electronic to pneumatic transducers. Calibration of sensors is mathematical; consequently the total man-hours for calibration are greatly reduced. The central diagnostic capabilities are a significant asset. Software and programming are constantly improving, becoming increasingly user-friendly with each update.

Benefits of DDC


The benefits of direct digital control over past control technologies (pneumatic or distributed electronic) is that it improves the control effectiveness and increases the control efficiency. The three main direct benefits of DDC are improved effectiveness, improved operation efficiency and increased energy efficiency.

Improved Effectiveness
DDC provides more effective control of HVAC systems by providing the potential for more accurately sensed data. Electronic sensors for measuring the common HVAC parameters of temperature, humidity and pressure are inherently more accurate than their pneumatic predecessors. Since the logic of a control loop is now included in the software, this logic can be readily changed. In this sense, DDC is far more flexible in changing reset schedules, setpoints and the overall control logic. Users are apt to apply more complex strategies, implement energy saving features and optimize their system performance since there is less cost associated with these changes than there would be when the logic is distributed to individual components. This of course assumes the user possesses the knowledge to make the changes.

DDC systems, by their very nature can integrate more easily into other computer-based systems. DDC systems can integrate into fire control systems, access/security control systems, lighting control systems and maintenance management systems.

Improved Operational Efficiency
Operational improvements show the greatest opportunity for efficiency improvements in direct digital controls. The alarming capabilities are strong and most systems have the ability to route alarms to various locations on a given network. The trending capabilities allow a diagnostic technician or engineer to troubleshoot system and control problems. They also allow the data to be visualized in various formats. These data can also be stored and analyzed for trends in equipment’s performance over time.

Run-times of various equipment can be monitored and alarms/messages can be generated when a lead/lag changeover occurs or if it is time to conduct routine maintenance.

The off-site access/communication capability allows an owner/operator to access their system remotely. Multiple parties can also be involved in troubleshooting a problem. The control vendor, design engineer and commissioning authority can use these features to more efficiently diagnose and visualize problems.

Increased Energy Efficiency
There are many energy-efficient control strategies employed in pneumatic logic that can be easily duplicated in DDC logic. Due to the addition of more complex mathmatical functions (easily obtained in software), there are many additional energy-efficient routines that can be used with DDC.

Strategies such as demand monitoring and limiting can be more easily implemented with DDC systems. The overall demand to a facility can be monitored and controlled by resetting various system setpoints based on different demand levels. If a DDC system is installed at the zone level, this could be accomplished by decreasing the requirement for cooling on a zone-by-zone basis.

By storing trends, energy consumption patterns can be monitored. Equipment can also be centrally scheduled “on” or “off” in applications where schedules frequently change.