Senin, 12 Desember 2011

Metering Software ( Custody Sales Metering )


General Signal Flow Diagram
   Flow compuer selection signal is sent from selection swithch of Metering Panel  to PLC. PLC controls MOV to perform auto swithcing by refering to flowrates from selected flow computer. G/C controller sends Gas composition data to flow compuer for volume correction and density calculation. HMI PC communicates with each flow computers and saves process data. G/C operation PC is used for monitoring chroatogram, G/C status and G/C calibration.
Metering System General Signal Flow Diagram

General Application Software Configuration

Application softwares  consist of HMI, I/O Serverand Report Program. HMI program communicates with Report Program by DDE. So HMI can print control of Report Program like a automatic hourly,daily, monthly report print and manual print. General MODBUS I/O Server only supports 32bit single precision floating format. However MReport suports 64bit double precision floating format and directrly commuicate with flow computer.

Metering System Application Flow Diagram
HMI Example Screen and MReport Program
Following example is  orifice type station has 4 meter run. Each meter run has MOV so that auto meter run switching or manual valve operation is possible. Flow computer is hot/stand-by configuration. This natural gas station has 1 G/C to send gas composition data to flow compuers.

Orifice Gas Metering System HMI Screen Example
MReport  ( Gas Metering System Report Program )
HMI Main Screen
MReport Program

Jumat, 11 November 2011

Multi-Coal Fired Boiler Optimum Control


Multi-Coal Fired Boiler Optimum Control uses a proprietary algorithm from MHI. It monitors the characteristics of coal and the status of combustion in the boiler based on the heat balance of each heating surface of the boiler to support optimum control. This function runs on an operator station (OPS) from DIASYS Netmation.

Features

  • A large number of successful deliveries
    Since the first delivery in 1997, a large number of Multi-Coal Fired Boiler Optimum Control systems have been delivered for Mitsubishi supercritical-pressure variable-pressure once-through boilers.
    Parts of this system have also been delivered for drum type boiler plants.
  • Changing parameters is not necessary when coal types are switched
    The control parameters of the boiler are automatically set based on estimates of the state of the heating surfaces of the boiler. Consequently, changing parameters whenever a different coal type or coal type group is used is no longer necessary.
    Multi-Coal Fired Boiler Optimum Control can automatically set the control parameters for a boiler even when blended coal is used.
  • Shorter adjustment period when a new type of coal is used
    Even when a new type of coal is decided to be used, if it can be burned mechanically by adjusting combustion, Multi-Coal Fired Boiler Optimum Control can reduce or even eliminate the APC adjustment period.

Functions

Multi-Coal Fired Boiler Optimum Control offers the following functions.
Item Brief description
Characteristics change by coal type
(heat absorption characteristics, generated heat)
Estimation of the heat absorption distribution
(heat absorption index)
If the heat absorbed by each heating surface is estimated, the control parameters can be adjusted for the heat absorbed by the boiler. Consequently, compared to the case where the control parameters are switched based on a coal type group, more precise control parameters can be fed.
Adjustment for generated heat If the heat absorbed by each heating surface is estimated, the heat input from the coal and air and the heat output to the gas at the boiler exit can be calculated online. Based on the heat input and output, the generated heat can be estimated, and the fuel parameters can be adjusted in a precise manner.
Estimation of the moisture content of the coal The moisture content of the coal can be estimated from the heat balance in the mill. Using this estimation along with the mill current and roller lift, you can get the characteristics of the columnar coal and automatically set the parameters related to the mill, such as the mill exit temperature, the rotation speed of the mill rotating classifier, and the oil pressure of the mill pressure device.
Estimation of the mill load ratio By using model calculations based on a mill model, the hard grove index (HGI) can be estimated. By using this estimation along with the estimate of the moisture content of the coal, you can adjust the reference capacity of the mill, and you can estimate the mill load ratio from the actual amount of supplied coal.
Boiler characteristics change over time Estimation of the cleanness of the heating surfaces If the heat absorbed by each heating surface is estimated, the thermal conductivity can be calculated online. As the combustion in the boiler continues, the thermal conductivity decreases. Optimum timing of activating soot blowers should be based on time and also on the thermal conductivity as a good indicator.

System Configuration

  • Real-time calculation based on fuzzy logic
    The state of heating surfaces can be estimated based on fuzzy logic. The effect of a coal type can be calculated with high precision in real time from the absorbed heat.
  • Constructed from software logic
    The whole Multi-Coal Fired Boiler Optimum Control can be constructed with DIASYS software logic using the Mitsubishi Interpreter DDC Oriented Language (Mitsubishi IDOL).
  • Easy extension from a preexisting system
    Except for a few sensors(Note), all sensors necessary for Multi-Coal Fired Boiler Optimum Control are already built into a plant control unit (APC).
(Note) RH spray water flow meter, primary RH entrance steam flow meter, and denitrification entrance gas temperature sensor

Specifications


Hardware specifications

The specifications of the hardware necessary for Multi-Coal Fired Boiler Optimum Control are as follows.
Item Specification
Model DIASYS Netmation(duplexed CPU, single PIO system)
Structure IP-33(dust-proof, water-proof)
Conditions 0 - 54 deg C / 90%RH or less
Num of boards/Dimensions 1board / 800mm(W) x 800mm(D) x 2300mm(H)
Insulation resistance 500VDC / 5MΩ or greater
Power supply-FG or I/O modules-FG
Withstand
voltage
Power supply-FG 2000VAC/1minute
Digital I/O terminal-FG 1500VAC/1minute
Analog I/O terminal-FG 500VAC/1minute
Coating External,internal,channel base : Munsell 5Y7/1(half gloss)
Other feature Dedicated maintenance tool and gateway device
(to interface with systems other than DIASYS Netmation)

Software specifications

The specifications of the software necessary for Multi-Coal Fired Boiler Optimum Control are as follows.
Item Variable-pressure
once-through boiler
Constant-pressure
once-through boiler
Drum boiler
Description lunguage Mitsubishi Interpreter DDC Oriented Language(IDOL)
Operating speed 100msec
Number of control roops Depends on the mounted features and existing system.
Absorbed heat quantity index Available(load change test with at least 3 coal types is required) Not available
Heating value adjustment Availbale Not available
Heating surface fouling Detected
Moisture percentage in coal Detected(estimated for each mill)
Mill load factor Detected(estimated for each mill)

Metering System




General System Configuration

Metering System consists of flow meter, flow calculator panel, G/C and HMI application softwares. Flow calculator panel has flow computer, PLC, G/C Controller.
Flow compuer performs  calculation of flowing density, volume correction, mass flowrate, corrected volume flowrate and energy flowrate by refering to gas component,  pressure, temperature  in case of natural gas.  PLC performs automatic meter run switching or manual valve operation. Also PLC communicates with upper control system like MCS or RTU. HMI application enables user to easlily operate system. Please refer to Metering Software part for more details.
Gas Metering System General Configuration Diagram
Metering System Panel

Metering Panel (or Flow Calculator Panel)  is different as system configuration or user requirements. However basically includes flow computer, G/C controller and PLC.

Flow Computer Panel
Flow Calculator Panel
Flow Computer Panel

Gas Chromatograph
The gas chromatograph is used to obtain on-line composition information of selected process streams for current process operation. The gas chromatograph must operate automatically with a high degree of reliability, require a minimum of maintenance, and perform the desired analysis within the required time. Gas composition is used for density calculation and energy calculation.
The analyzer includes a chromatographic column(s), sample injection and switching valves, a detector, a temperature controller, flow controls for the carrier and detector medium(s), and the necessary electronics. The controller function may be separate or may be in the field with the analyzer, which thereby becomes a stand-alone gas chromatograph. Both systems provide analog outputs for concentration data and digital outputs for alarms, external stream select, and other external functions.
The thermal conductivity detector (TCD) is the most widely used because of its universal response to all components and its simplicity. The detector measures the thermal conductivity of the gas passing through it. The carrier gas is selected to have a thermal conductivity different from the components being measured. Helium or hydrogen is normally used for this reason.
GC ( Gas Chromatograph General Configuration )
GC (Gas Chromatograph) Panel
Gas Chromatograph Panel
Applied Standard
  • Orifice Meter : AGA 3, ISO 5167
  • Turbine Meter : AGA 7
  • Ultrasonic Meter : AGA 9
  • Density & Compressibility Calculation : AGA 8
  • Energy Calculation : ISO 6976 

Senin, 10 Oktober 2011

Sampel Conditioning System for Analyzer




Basic Concept and Construction of SCS
Sample conditioning systems are comprised of all the components necessary to extract a representative sample and to condition the sample for measurement by the analyzer. The design of the total sample conditioning system must be engineered for each specific application. The sample conditioning system assembly tends to be complex (actually small chemical processes with control systems) and is often the least reliable segment of an analyzer system. It is important that all factors that influence an overall system and the operation of an analyzer be given thorough consideration. Such factors as unknown process conditions, process upsets, and contaminants can lead to poor designs.

Primary Conditioning System
Installation of primary conditioning systems at the sample tap typically allows for more reliable operation of extremely difficult samples that cannot be transported easily to a remote sample conditioning system. Remote pressure let-down and vaporizer regulator stations are another type of primary conditioning system. These stations must be mounted near the sample tap to flash liquid samples and reduce lag times by controlling the sample pressure before transport to the analyzer location. Insulation of a heated enclosure may be required on these installations if the sample dewpoint temperature cannot be maintained.



Sample Probe
Sample probes should be used because they provide a more representative sample due to the higher flow rates away from process pipe walls.
Note: Process lines smaller than 2 in. usually do not require a sample probe. If a probe is required for small diameter lines, the line may be swaged up to 3 in. or larger with a spool piece to allow a probe to be inserted.
Sample probes significantly reduce wall contaminates and particulates and act as a first stage of filtration and conditioning. Special design considerations are required when process velocities are excessive (which may require thickwalled probes and in high temperature applications). Corrosive service or high temperatures may require special alloys or materials. Flanged thermowells are often used as sample probes by merely cutting the end off at a 45° angle. The probe is positioned 180 degrees from the process flow to minimize particulate matter in the extracted sample.


  Transport Line
In some installations, where the analyzer and sample system must be located at a distance from the sample point, the sample transport time must be considered. The time necessary to transport the sample to the analyzer can in some cases contribute the largest share to the overall system dead-time or turnaround time. Turnaround time is defined as the total time of sample system lag, dead-time, and the analyzer response time. A convenient means for reducing this transport lag is the use of a fast loop between the process equipment, an intermediate location (commonly just outside the analyzer shelter), and a low pressure return point in the process where the sample can be returned. Sample transport time, or lag time, is a function of the sample line length and diameter, the absolute pressure in the line, and the sample flow rate. Sample transport time is simply the total volume of the sample line divided by the average flow rate in the line. The lag time can be calculated with the aid of the following equations:


SAMPLE CONDITIONING SYSTEM Design
The functions performed by the sample conditioning system as the interface between the process and the process analyzer include the following:
  • Taking and delivering a representative sample from the process.
  • Transporting the sample from the sample tap to the analyzer and from the analyzer to the waste disposal and/or process return point.
  • Conditioning the sample by adjusting the pressure, temperature, flow rate, filtering, and phase maintenance of the sample as required to make the sample compatible to the process analyzer.
  • Sample-stream switching and calibration switching into the analyzer.
  • Design incorporates capability for ease of maintenance, cleaning, or (when needed) flushing the entire system.
The complete stream composition of all the components and contaminants must be considered. Some contaminants, such as solids or entrained liquids in a gaseous stream, may have to be removed by the sample system. The process conditions and range of all components during normal and especially abnormal conditions (such as startup, shutdown, rate change, and so forth) must be considered for the analyzer application and sample system design.




Analyzer System Package Photo




Referenced Documents
  • API RECOMMENDED PRACTICE 555 SECOND EDITION, NOVEMBER 2001 ANSI/API RP 555-2001
  • Process Stream Analysis (Analyzer Sample Systems), A Review of Basic Design Consideration. (Emerson)

Senin, 08 Agustus 2011

Difference between and RTU and PLC with DNP3 Protocol

RTU is focussed on responding to supervisory control sequences from multiple masters / slaves where comms can fail at any time.


PLC has no inbuilt resilience or fall back plan for comms failures or recovery
Polling protocols are expected to return information  in sequence with the computation cycle
DNP3 Protocol
One of the most common SCADA protocols in use today
Supported by DNP3 User Group
Full featured providing
Buffered Data (SOE)
Time Stamps
Quality Processing
Rich data types
Compatible with SCD5200, SCD2100, SCD2200, most 3rd party devices
Driver is integrated, full featured, supports triple redundancy and full SOE

Jumat, 22 Juli 2011

Automatic Custody Transfer System for Unmanned LNG Station

INTRODUCTION

Natural gas (NG) has become an important part of the energy mix, particularly in electric power generation, where it’s prized as an easily handled, clean-burning liquid. Liquefied Natural Gas (LNG) is a more cost-effective way to bring gas to market across oceans and continents. Construction of many overland pipe-lines is underway, but gas companies are also investing in LNG supply chains, building massive LNG tankers to convey gas from port to port, and terminals to convert gas to its form for easy transport, and back to gas for consumption. In this Paper, we’ll analyze the challenges of Flow measurement at LNG service applications.

COMMON LNG FACILITIES POSE METERING CHALLENGES

Flow meters used in LNG custody transfer should have the following as minimum requirements.

  • Low Pressure drop to avoid LNG vaporization.
  • No moving Parts.
  • The ability to perform in the cryogenic applications.
  • Proven ability & accuracy in liquid custody transfer applications.
  • As in custody transfer applications flow measurements also need to be verifiable with    check meters and provers.

EVALUATING FLOW METERS FOR LNG MEASUREMENT

Two different meters can satisfy the previous said requirements.

  • CORIOLIS
  • ULTRASONIC
From field tests conducted at an LNG facility in Alaska, users were able to determine how accurate the meters were by comparing flow measurements to level measurements in the LNG dispensing tanks and onboard a receiving LNG tanker. Under test conditions both meters offered similar accuracy and good repeatability.

WHAT IF A CORIOLIS FLOW METER IS INSTALLED?

  •       When a coriolis flow meter is installed, typically dual bent-tube designs are used to ensure the highest possible performance, causing pressure to drop and the risk of vaporization resulting multiphase fluid, which makes it difficult to measure and can introduce significant measurement uncertainty.

  •            Coriolis meters, while immune to changes in flow profile, are only available in diameters up-to 10” sizes.

  •             While a coriolis meter is a good choice for smaller line sizes and highly accurate in mass measurement several flow meters would be required to maximize throughput.
WHAT IF AN ULTRASONIC FLOW METER IS INSTALLED?


  •       Ultrasonic flow meters on other hand, have a straight flow path and do not obstruct or impede the gas or liquid flow through a pipeline.

  •             The result is essentially a no pressure drop and reduced risk of vaporization, results in good accuracy of measurement.

  •       They are also available in larger diameter sizes than coriolis meters, making them a more cost effective alternative for LNG applications, where pressure drop and maximizing throughput are prime considerations.


CONCLUSION

Ultrasonic flow meters offer the right technology and value proposition for custody-transfer applications. The high accuracy and low maintenance profile for capital investment in the oil & gas industry, will propel the ultrasonic flow meter market to double digit growth rates.


Expected Benefits

- Safe installation at hazardous remote sites. 
- Auto fleet identification at unmanned fuel stations.  
- Auto compensation to base temperature using a customized equation. 
- Automatic e-mailing of compiled daily dispense report to office via GSM/GPRS. 
- Web-based HMI that displays dispensing and tank status at remote site and enables upload and   set-up of  daily report.

Process Description

When a truck refuels at an unmanned station, the driver presses the start button and the message "Enter ID number" is displayed on the local HMI. When the ID entered at the local HMI is authenticated by the controller, the LNG dispensing sequence starts. The controller starts a pump to circulate liquefied gas and cool down the flowmeter. LNG is then dispensed to the truck. Then, the controller compensates the flow volume using a customized equation for custody transfer based on the measured temperature and pressure. On completion of each dispense, flow data is saved in the controller as a file. At the end of the day a report is created by compiling all the day' s dispenses on the controller and is automatically e-mailed to the office for billing purposes.

Application Solutions

Yokogawa provides an innovative automatic custody transfer system for unmanned LNG fuel stations that uses the STARDOM FCN controller and a cryogenic version vortex flowmeter.

Safe installation

LNG that vaporizes and mixes with air in the proper proportions can ignite. To prevent accidents at remote gas stations, the controller is stored in a cabinet with an intrinsically safe barrier.

Fleet identification

An ID file storing fleet ID information has been loaded onto the controller and can be modified online by accessing the controller web page. When the truck driver presses the start button, "Enter ID number" is displayed on the local HMI. When the fleet ID number is entered into the local HMI, the ID number is sent to the controller and compared with the ID information in the file. When the ID is authenticated, the controller initiates the LNG dispensing sequence. However, if the ID is not authenticated, an error message is displayed on the local HMI.

Liquefied gas dispensing

1. After the ID is authenticated, the controller starts a pump to circulate liquefied gas through the pipe until the temperature falls low enough for single-phase liquid flow. If this cannot be achieved within a given time frame, the controller stops the pump, displays an "error" on the local HMI, and returns to idle.

2. When the temperature is low enough, the controller opens the valve and slowly ramps up the pump speed to avoid tripping due to sudden increases in back pressure. During the dispensing, the pressure is monitored and, if it goes high (due to back pressure problems or the tank being full), filling stops. If the truck has more than one tank to fill, the local HMI prompts the driver to connect to the next tank and continue filling. Once completed, the local HMI displays the total amount dispensed, and a report is created in the controller.


Flow volume measurement

The Yokogawa DY cryogenic version vortex flowmeter handles process temperatures as low as -200 deg C with high accuracy (liquid: ±0.75%).

Flow correction

Flow (measured by the Yokogawa cryogenic version vortex flowmeter) as well as temperature and pressure are transmitted to the controller. The flow is compensated to the base temperature using a customized equation for custody transfer.

Logging file

On completion of each dispense, the corrected flow, temperature, and pressure are saved as an Excel compatible CSV file in the controller's compact flash memory. This log file can be uploaded on demand to a PC using the FTP function and can also be viewed in trend format by accessing the controller web page.

Report file

At the end of the day, a report file is created by compiling all the day's dispense files. As a default, two daily reports are provided. These are (1) Daily Dispense Report: summary of the day's dispenses, and (2) Daily Status Report: tank level and pump usage. These reports are in Excel compatible CSV format and are completely user definable. The created daily reports are e-mailed to an office for billing purposes via GSM/GPRS or some other Internet connection. Also, these reports can be uploaded on demand to a PC using the FTP function and can be opened in Microsoft Excel.

Web-based HMI

The following pages can be accessed at the controller URL: Tuning Parameter Setting: Without the modification of applications, parameters can be set on this parameter web page. These include timer set points, pressure set points, alarm set points, and PID tuning parameters. Also, data logging and report creation configuration can be set.
Dispense Trend: The dispensed quantity and historical trend can be monitored in real time.
Site Status: Gas station status information such as storage and dispensing quantity and status can be monitored.

Alarm notification via e-mail

If an alarm occurs, the controller immediately sends to a specified person an alarm e-mail that contains a log of all process parameters at the time of the alarm.

Kamis, 09 Juni 2011

Menghitung Harga PLTS



Kalkulasi $/kWh dari sistem PLTS ini melibatkan dua komponen, yaitu:

1. Upfront cost: harga yang harus dibayarkan untuk pemasangan sistem PLTS di awal.

2. Life cycle cost: harga yang harus dikeluarkan agar sistem dapat beroperasi dalam jangka waktu tertentu (misalnya selama 20 tahun). Life cycle cost yang paling utama adalah battery. Jika batery dapat bekerja dalam jangka waktu 4 tahun, maka dibutuhkan 5 kali penggantian batery agar sistem dapat beroperasi selama 20 tahun.

I. PERHITUNGAN UPFRONT COST


Untuk sistem PLTS off-grid, komponen upfront cost terdiri dari harga inverter (atau inverter + charger), harga panel, dan harga baterai. Perhitungan masing-masing komponen adalah sebagai berikut:

1. Harga inverter/charger ~ $ 1000/kW
2. Harga solar panel ~ $ 2000/kW
3. Harga battery (upfront cost) ~ $ 1000/kW
4. Harga lain-lain (kabel, box, frame) ~ $ 1000

Total upfront cost ~ $ 5000 / kW

II. PERHITUNGAN LIFE CYCLE COST

Komponen utama life cycle cost adalah battery. Untuk masa operasi 20 tahun, diasumsikan terjadi pergantian batery sebanyak 5 kali, sehingga:

Harga battery (life cycle cost) = 5 * $1000 = $ 5000

Total Life cycle cost = Harga inverter/charger + harga solar panel + harga battery (life cycle cost) + harga lain2 = Total Life cycle cost = $ 1000 + $ 2000 + $5000 + $ 1000 = $ 9000

Perhitungan selanjutnya adalah menentukan total kWh yang digunakan selama sistem bekerja. Dengan menggunakan asumsi sistem bekerja selama 20 tahun dan energi yang digunakan adalah E_used, maka:

Total kWh = 20 tahun * 365 hari * E_used = 7300 * E_used

Jika untuk sistem yang mampu menghasilkan daya maksimum sebesar 1 kW, energi yang digunakan diasumsikan sebesar 5 kWh, maka:

Total kWh = 20 tahun * 365 hari * 5 kWh = 36500 kWh

Dari data-data ini, maka perhitungan $/kWh dapat dihitung sebagai berikut:

Cost_kwh = (Total life cycle cost) / (total kWh) = ($9000) / (36500 kWh) = $0.24/kWh atau 24 sen/kWh.

Sabtu, 14 Mei 2011

SYSTEM PLANNING SOLAR TECHNOLOGY

The following documents and design tools are aimed at electricians, solar technicians, and professional planners. They offer interesting additional information for all relevant questions regarding the planning of PV systems.

DIRECT CURRENT ( DC ).

Ground connection for thin-film modules and back-contact PV modules


String fuses/reverse current


Module technology


Discharge currents


SOLAR INVERTERS
.

Product overview


Texts for Invitation

  • Text for invitation of Sunny Boy / Sunny Mini Central / Sunny Tripower (XLS)


System design


Grid interface




Senin, 02 Mei 2011

Solar Energy Advantages Disadvantages

This page is a review of the technological and economical of solar energy advantages disadvantages. The advantages get a lot of publicity, to balance the picture the disadvantages and limitations are highlighted.

Advantages of Solar Energy

In this section I will discuss the solar energy advantages, disadvantages will be discussed in the next paragraph. The advantages are:

  • Residential solar power generators are silent.
  • Photovoltaic generating systems have no moving part therefore they require a very low maintenance effort, they are reliable and the life expectancy of solar generators can exceed 20 years.
  • Domestic solar electricity generation systems do not emit polluting gases and do not produce carbon dioxide. It is expected (we already see the initiatives in Europe) that taxes will be imposed on carbon dioxide emissions. You can preempt these future carbon dioxide taxes by installing a residential solar power system and a domestic solar powered hot water heater.
  • Once the initial investment is covered, electricity supply from the solar generator is effectively free of charge. Based on the last decade trend and with the political turmoil in the Middle East, it is expected that utility electricity will be more and more expensive in the future to reflect the higher prices of fuel; therefore securing a free of charge electricity during the expected future escalation of energy prices is really a benefit

Advantages of Solar Energy

In this section I will discuss the solar energy advantages, disadvantages will be discussed in the next paragraph. The advantages are:

  • Residential solar power generators are silent.
  • Photovoltaic generating systems have no moving part therefore they require a very low maintenance effort, they are reliable and the life expectancy of solar generators can exceed 20 years.
  • Domestic solar electricity generation systems do not emit polluting gases and do not produce carbon dioxide. It is expected (we already see the initiatives in Europe) that taxes will be imposed on carbon dioxide emissions. You can preempt these future carbon dioxide taxes by installing a residential solar power system and a domestic solar powered hot water heater.
  • Once the initial investment is covered, electricity supply from the solar generator is effectively free of charge. Based on the last decade trend and with the political turmoil in the Middle East, it is expected that utility electricity will be more and more expensive in the future to reflect the higher prices of fuel; therefore securing a free of charge electricity during the expected future escalation of energy prices is really a benefit

Jumat, 15 April 2011

Off-Grid Solar Power System

This system will deliver a maximum of 180 watts/15 amps of power via each of two 12-volt cigarette lighter sockets, 140-150 watts of continuous 120VAC/60Hz pure sine wave power via a power inverter, and is wired and fused accordingly. The maximum combined deliverable power at any given moment is approximately 300 watts, limited by the drop in the battery voltage at a discharge current of approximately 25 amps, and is protected against over-current by a 30-amp ATC fuse. If the combined power draw of your electronic devices is 60 watts, the battery will last approximately 4 hours in the absence of incoming solar power before it needs to be recharged, longer if the power draw is less. If the current draw from either of the cigarette lighter sockets exceeds 15 amps, a 15-amp ATC fuse will blow, and will need to be replaced (simple to do; extras included). If the power draw from the inverter exceeds its continuous or surge wattage ratings, it will turn off, and then will need to be re-set (switch inverter power button off, then back on), or a 20-amp ATC fuse will blow and will need to be replaced (extras included).

The battery, solar charge controller, power inverter, 12-volt DC power distributor, wiring, and accessories are housed in a water-, crush-, and dust-proof, protective carrying case in black. The power system components are secured and padded inside the case by custom-configured cubed foam. The solar panel remains outside of the case. Off-Grid Solar Power System - #1 comes with: Battery: 26 amp-hour (312 watt-hour), adsorbed glass mat, sealed lead acid. Solar Charge Controller: 7-amp unit that is protected by a 7.5-amp ATC fuse. Power inverter: continuous 150-watt, pure sine wave unit that is protected by a 15-amp ATC fuse. Solar panel: one foldable 72-watt unit that weighs 6.4 pounds, and that will require 5-6 hours of peak sunlight to recharge the battery from empty to full. To charge the battery via a standard AC receptacle, included is one 3-amp, AC-powered battery charger. To charge the battery via an automobile 12-volt DC cigarette lighter socket, included is one male DC plug with cable.


The case measures 18.50 x 14.06 x 6.93 inches in external dimensions, and the entire system weighs approximately 37 pounds.


This system will deliver a maximum of 180 watts of power/15 amps via each of two12-volt cigarette lighter sockets (limited by 15-amp fuses), 150 watts of continuous 120VAC/60Hz power via an inverter (limited by the inverter circuitry), and is wired and fused accordingly. The maximum combined deliverable power at any given time is 360 watts/30 amps, and is limited by a 30-amp ATC fuse. If the combined power draw of your electronic devices is 60 watts, the battery will last approximately 3.5-4 hours in the absence of incoming solar power before it needs to be recharged, longer if the power draw is less. If the power draw from either of the cigarette lighter sockets exceeds 180 watts, a 15-amp ATC fuse will blow, and will need to be replaced (simple to do; extras included). If the power draw from the inverter exceeds its continuous or surge wattage ratings, it will turn off, and then automatically reset itself, or a 20-amp ATC fuse will blow and will need to be replaced (easy to do; extras included).

The battery, solar charge controller, power inverter, 12-volt DC power distributor, solar panel, wiring, and accessories are housed in a water-, crush-, and dust-proof, protective carrying case in yellow. The power system components are secured and padded inside the case by custom-configured foam. Off-Grid Solar Power System - #2 comes with: Battery: 26 amp-hour (312 watt-hour), adsorbed glass mat, sealed lead acid. Solar Charge Controller: 7-amp unit protected by a 7.5-amp ATC fuse. Power inverter: continuous 150-watt, modified sine wave unit. Solar panel: one foldable 72-watt unit that will require 5-6 hours of peak sunlight to recharge the battery from empty to full, and that weighs 6.4 pounds. To charge the battery via a standard AC receptacle, included is one 3-amp, AC-powered battery charger that is protected by a 5-amp ATC fuse. To charge the battery via an automobile 12-volt DC power socket, included is one male DC plug with cable.

Kamis, 31 Maret 2011

Smarter Metering

Technologies for T&D Networks

Microsoft Word - MIPRO-Croatia_TWTcomments_2006.doc
 “Smart metering” has demonstrated how advances in technology may be used to solve a utility's changing needs in a dynamic market- place. But where smart metering is effective at the end-customer metering point, new technologies in multifunction “smarter meters” provide a broader range of benefits at any metering point within a utility network.  
This paper describes how new communications technologies  including local mastering, gateway functionality, web based presentment, e-mail data transfers and Ethernet support of SCADA protocols  have been used by power utilities around the world to provide integrated network control and monitoring.
With these technologies, communications costs to remote substations are drastically reduced while still increasing the number of monitored points and improving network awareness. It is shown how these communication links can provide billing data, operational data to supervisory control and data acquisition (SCADA) systems, and regulatory compliant power quality information so that the needs of multiple departments are met within a single device.            
Finally, case studies are presented that illustrate how utilities leverage smarter meters to automate tasks such as local aggregation and advanced transformer compensation to simplify network analysis and billing. By providing distributed intelligence, local control and the communications infrastructure to reach more metering points, Smarter metering enables utilities to increase awareness, reduce risk, and lower operational costs.          
I. History of Smart Metering           
Since the introduction of solid-state metering in the early 1990s, features have been added to tariff meters to provide more valuable information to electric utility companies than simple energy accumulation.
Multifunction meters register active, reactive and apparent energy, time-of-use (TOU) meters track energy consumption at different tariff rates, and remote communications options (fixed network or wireless) have been added for automated meter reading (AMR). A device with the embedded intelligence required to offer these combined features has often been dubbed a “smart meter”.               
Smart metering is typically applied at the end customer metering point, be it industrial, commercial or residential, and primarily for billing purposes only. While this covers the largest number of monitoring points in a utility’s network, no additional features are provided where energy flows are largest and operational data is most critical: within the transmission and distribution network.                
Recently, “smarter”, more powerful meters have begun to emerge that offer better interface technologies. These provide access to more information than their earlier “smart” counterparts:    
SCADA data, power quality and reliability data, loss calculations and error correction, and other troubleshooting data. These new communication technologies can be used to connect to remote mission critical transmission and distribution (T&D) stations, or between devices within these stations.          
II. New Communication Technologies             
To the substation:        
Slow, not broadband, power line carrier (PLC) and serial data modem lines have long been used for remote access to substation data. While effective for basic SCADA telemetry, these media are limited to relatively low throughput rates, generally below 9600 bps. Capacitor traps for PLC systems are expensive to install and maintain, and modem lines are susceptible to electro magnetic noise leading to suboptimal communication rates. For both of these traditional media, complex data types such as digital waveform recordings lead to long connection times and limit a utility’s ability to read all of their installed meters in a timely fashion.                 
With the growth of wide area networks and the world-wide web, TCP/IP has emerged as a high throughput transportation mechanism suitable for many new media and embedded protocols.  Ethernet connections (either twisted pair copper or fibre optic) provide dedicated 10 or 100 Mbps channels capable of addressing all devices within a substation simultaneously. With a data transfer rate 1000 times faster than dial-up modem, TCP/IP can support complex data types without introducing communications bottlenecks. Fibre optic links provide the additional benefit of galvanic isolation, removing a potential failure point from the system.                
For remote substations, TCP/IP can be utilized over satellite radio links or broadband power line carrier. In either case, the telecommunications industry has provided the necessary equipment to transmit and decode these signals, simplifying installation and removing integration conflicts.       
The TCP/IP address of the end device is all that is needed to configure the system. Finally, email may be used as a transportation mechanism. Relying on TCP/IP for transmission of the individual packets, e-mail allows data to flow seamlessly through firewalls without compromising security.
The information technology (IT) industry has developed systems to accommodate the flow of email traffic while maintaining the security of their networks. Email is preferred in many cases by IT departments than TCP/IP connections alone because of the enhanced security it offers.  Smarter meters supporting TCP/IP provide access to all of these communication architectures and the development efforts of the entire communications industry.
Within the substation:              
Ensuring a high throughput communications    pipeline to the substation is the highest priority in ensuing timely access to metering data. But within the substation, new technologies are also                present to reduce the installation cost and improve access to other substation devices.       
Ethernet and modem gateways allow one smarter meter to act as a communication hub, routing messages to other devices in the substation over inexpensive RS-485 serial connections (Figure 1). 1). Using such an architecture, only one device needs to be equipped with either the Ethernet or modem hardware, reducing the overall cost of the metering equipment and allowing access to 32 downstream devices or more. When using an industry standard protocol such as Modbus or DNP, the downstream devices are unaware that the request has been passed through a gateway and behave as though communicating directly to the master software or RTU. Older devices can thus be integrated into a newer communications architecture.                
Microsoft Word - MIPRO-Croatia_TWTcomments_2006.docMicrosoft Word - MIPRO-Croatia_TWTcomments_2006.doc
Microsoft Word - MIPRO-Croatia_TWTcomments_2006.doc
Figure 1. Using gateways to communicate with devices inside a substation.
Microsoft Word - MIPRO-Croatia_TWTcomments_2006.doc
Another means of integrating legacy devices is through local mastering. In this application, a smarter meter is used as an RTU; requesting information from other devices and passing it backbup to the master software. This opens up possibilities for local data control, such as aggregating feeder readings from multiple devices before transmission back to the master software. 
 Microsoft Word - MIPRO-Croatia_TWTcomments_2006.docFinally, for data acquisition systems that include transducers without communications capability, smarter meters are available with onboard analog inputs that can directly interface with the output signal of each transducer. Values can be aggregated from multiple transducers and scaled appropriately before transmission to the master software.


Microsoft Word - MIPRO-Croatia_TWTcomments_2006.doc
Figure2. New communication technologies simplify collection of data from existing and new substation devices.
Microsoft Word - MIPRO-Croatia_TWTcomments_2006.doc
III. Extended Interoperability and Data         
Access New communication technologies can solve many problems related to data acquisition and speed, but the benefits to utilities are only realized if the information is presented in a ready to use format. Integration with existing utility systems is key to meeting this need.         
For each user, system or department, smarter meters present information in the appropriate format over appropriate media. SCADA and Operations systems require industry-standard protocols such as IEC 61850, IEC 60870-5-101, DNP or Modbus. Various device vendors make          these protocols available over TCP/IP for high speed direct integration into existing SCADA systems.     
Billing systems may require information on energy consumption or demand in protocols such as DLMS, IEC 60870-5-102 or MV90. Again, some software vendors now support data acquisition over TCP/IP using these protocols.  In addition to these more traditional uses of data, key account managers may wish to view load profiles, power quality information or alarm conditions. For each of these, the data format and media is customizable, ranging from pager alerts to emailed reports, to web-accessible graphical views.    
Finally, other utility departments may wish to view the information contained in a smarter Mmeter. By providing a secure web server on the device, authorized persons can view critical information in real-time from any computer any where in the world        .
IV. Case Studies              
Using Ethernet to provide data to multiple users
After liberalization, a major utility needed to provide daily settlement data to the independent system operator (ISO). The utility chose smarter meters with TCP/IP support and gateway functionality. Forty gateway meters connected to the existing Ethernet wide area network provided high-speed access to over 260 new tariff meters.    
By using TCP/IP, there is no concern that the utility or ISO data retrieval will interfere with each other and the utility network now supports complex power quality data at any of its monitoring points.     
Using satellite to overcome geographical challenges
An electrical utility with a 70,000 square kilometre service area needed access to remote        substation data. Due to limited existing infrastructure, TCP/IP over satellite links provides access to real-time SCADA data. Transient events, sag/swell events and transformer loading alarms for the substation are sent by e-mail over satellite to PCs and pagers.                  
Using local mastering to increase efficiency
Managers at a switchyard needed combined instrument / transformer loss compensation and power factor monitoring, plus aggregation and scaling of real-time data. By monitoring transformer and instrument losses on the secondary side, installation costs are reduced without sacrificing accuracy.       
The switchyard is a 500kV transmission facility with 10 bays, handling power flowing to and from four different independent power producers, a nuclear facility, and several other      substations. Substation bays operate as four loops, with smarter meters configured as Mod-bus Master devices, each gathering real-time data from its loop to perform scaling and aggregation before passing values to a central RTU.
The network fully integrates with the existing billing system and provides a valuable backup function if the RTU or communication links fail, the data can be retrieved manually from the onboard non-volatile memory of each meter. When generators go online and merchant sites produce their own power, the breakers close and the meters go offline.  
             Microsoft Word - MIPRO-Croatia_TWTcomments_2006.docFigure 3 Information flow from smart meters    

Microsoft Word - MIPRO-Croatia_TWTcomments_2006.doc
V. Conclusion  
Applying the new technologies of the telecommunications industry to metering systems allows utilities to increase network awareness and control. Combining these technologies with powerful multi-function metering platforms provides opportunities for utilities to reduce operational risk, solve business needs, and improve network reliability.
Microsoft Word - MIPRO-Croatia_TWTcomments_2006.docFigure 4 Benefits of new “smarter meter” communications technologies